1What is IEC 62443?
IEC 62443 is the reference series of standards for the cybersecurity of industrial systems: programmable logic controllers (PLCs), supervisory systems (SCADA), distributed control systems (DCS), safety instrumented systems (SIS) and OT networks. It is published by the International Electrotechnical Commission (IEC) and stems from the ISA99 committee's work; it is also known as ISA/IEC 62443.
OT is not protected the way IT is: process availability and personnel safety come first, equipment lives for twenty years, and you do not reboot a PLC in production to apply a patch. The standard addresses these constraints with a zones and conduits approach rather than a single perimeter, and with security levels proportionate to the threat.
Its strength is to share responsibilities among three actors:
- the asset owner, who operates the facility and carries the risk;
- the system integrator and the maintenance service provider, who design, install and maintain the system;
- the product supplier, who develops the components: PLCs, software, network equipment.
2The parts of the series
The series is organised into four groups. The most widely used parts:
| Part | Content | For whom |
|---|---|---|
| 1-1 | Terminology, concepts and models | Everyone |
| 2-1 | Asset owner security program (cybersecurity management system) | Asset owner |
| 2-4 | Requirements for integration and maintenance service providers | Integrator |
| 3-2 | Security risk assessment and system design: zones, conduits, target levels | Asset owner, integrator |
| 3-3 | System security requirements (SR) and security levels | Integrator, supplier |
| 4-1 | Secure product development lifecycle | Supplier |
| 4-2 | Technical security requirements for components (CR) | Supplier |
For a facility project, the core of the work is the 3-2 โ 3-3 sequence: assess the risks, set a target security level for each zone, then derive the requirements to meet.
3Zones, conduits and security levels
A zone groups assets that share the same security requirements. A conduit groups the communications between zones: it is through the conduit that an incident spreads, so that is where it is contained.
Each zone and conduit is assigned a security level (SL), from 1 to 4, defined by the type of attacker it must withstand:
| Level | Protects against |
|---|---|
| SL 1 | Casual or coincidental violation |
| SL 2 | Intentional violation using simple means, low resources and generic skills |
| SL 3 | Intentional violation using sophisticated means, moderate resources and IACS-specific skills |
| SL 4 | Intentional violation using sophisticated means, extended resources and high motivation |
Three levels must not be confused:
- SL-T (target): the level aimed for, derived from the risk assessment;
- SL-C (capability): the level the components and the system can achieve when properly configured;
- SL-A (achieved): the level actually reached on the facility.
Levels are expressed against the seven Foundational Requirements: FR1 identification and authentication control, FR2 use control, FR3 system integrity, FR4 data confidentiality, FR5 restricted data flow, FR6 timely response to events, FR7 resource availability.
4The IEC 62443-3-2 risk assessment, step by step
Part 3-2 describes the process as seven requirements, labelled ZCR (Zone and Conduit Requirement):
ZCR 1 โ Identify the system under consideration (SUC)
Define the boundaries of the System Under Consideration: equipment, networks, data flows and access points. The usual medium is an architecture diagram.
ZCR 2 โ Initial cybersecurity risk assessment
Assess the worst realistic impact if the system were compromised, before any cybersecurity measure. It serves as the baseline for what follows.
ZCR 3 โ Partition into zones and conduits
Group assets into zones (by criticality, function, location) and identify the conduits between them. Safety functions (SIS) and devices connected to external networks are separated from the rest.
ZCR 4 โ Does the initial risk exceed the tolerable risk?
If so, a detailed assessment is required for the zones concerned.
ZCR 5 โ Detailed risk assessment per zone and conduit
Identify threats and vulnerabilities, assess impact and likelihood, then set the SL-T of each zone and conduit and define the countermeasures needed to bring the risk down to a tolerable level.
ZCR 6 โ Document the requirements (CRS)
Record in the Cybersecurity Requirements Specification the scope, the zones and conduits, the SL-Ts, the selected measures and the assumptions. It is the deliverable of the study and the input to design (Part 3-3 requirements).
ZCR 7 โ Asset owner approval
The asset owner validates the results of the assessment and formally accepts the residual risk.
5Example: a pumping station
A drinking-water pumping station includes a corporate network, a DMZ, SCADA supervision, two field networks (abstraction and distribution) and a safety instrumented system. A typical partition:
| Zone | Content | Indicative SL-T |
|---|---|---|
| Enterprise | Directory, ERP, office workstations | SL 1 |
| IT/OT DMZ | Historian, remote maintenance gateway | SL 2 |
| Supervision | SCADA servers, operator workstations | SL 2 |
| Field | PLCs, HMIs, industrial switches | SL 2 |
| Safety (SIS) | SIL 2 safety PLC | SL 3 |
The conduit between the DMZ and the Enterprise zone goes through a firewall, remote maintenance access goes through the DMZ only, and the SIS exchanges data with supervision in read-only mode. The levels shown are an example: each site justifies them through its own risk assessment.
This example is handled end to end in Polyodos: SUC diagram, zones and conduits, detailed assessment, SL-T per foundational requirement, Part 3-3 requirements and CRS report in Word format. See the IEC 62443 demo or try Polyodos free for 30 days.
6Common mistakes
| Mistake | Why it is a problem |
|---|---|
| A single zone for the whole OT scope | Defeats the purpose of segmentation: a safety PLC and a supervision workstation have neither the same criticality nor the same SL-T. |
| Confusing SL-T, SL-C and SL-A | SL-T is a goal, SL-C a capability, SL-A an observation. Mixing them hides the real gap to be closed. |
| Ignoring conduits | A well-protected zone linked by an uncontrolled conduit to a weak zone exposes the whole: the conduit is often the real weak point. |
| Transposing IT measures without adaptation | An automatic reboot or a patch applied without testing may be incompatible with process availability or safety. |
| Forgetting asset owner approval | Without formal acceptance of the residual risk (ZCR 7), the study remains a technical document with no decision. |